Measurement |
AC Voltage: |
L1: 85-277 Vrms
L2: 0-277 Vrms
L3: 0-277 Vrms |
DC Voltage: |
42 Vrms
Power: 9-60 Vdc
Measurement: +/-60 Vdc |
Current: |
15 channels
5-6900A max per channel
Fully isolated inputs |
Frequency: |
50 or 60 Hz |
Logging Values: |
V, A, W, Wh, Hz, VA, VAr, THD, deg |
Power Draw: |
12W max, 2W typical |
Environmental |
Op. Temperature: |
-30 to 70 deg C (-22 to 158 F) |
Max Altitude: |
4000m (13,123ft) |
Max Humidity: |
80% up to 31 deg C |
Meas. Category: |
Overvoltage Category III |
Location: |
Open type indoor device |
Pollution Degree: |
2 |
Data Logger Capacity |
Register Count: |
64 (data storage points) |
Granularity: |
1 hour/1 second |
(duration/avg) |
1 year/1 minute
10 yrs/15 minute
Device Lifetime/1 Day |
Safety and Regulatory |
Safety: |
IEC/UL 61010-1 Ed. 3.0 B:2010 |
CE: |
IEC 61000-6-1 Ed. 3.0 B:2016
IEC 61000-6-3 Ed. 2.1 B:2011 |
FCC: |
FCC Title 47 CFR Part 15-Subpart B Class B
ICES-003 Information Technology Equipment Class B |
Communication |
Homeplug AV: |
Compatible with Homeplug AV-adapter within ~100ft. on same phase as L1 |
Ethernet: |
IEEE 802.3 - LAN |
User Interface |
|
Compatible Browsers:
(Only up-to-date versions supported) |
Google Chrome
Firefox
Safari
Internet Explorer |
Enclosure |
|
Material: |
FRABS |
Dimensions: |
17 x 8 x 4.6cm
(6.7 x 3.15 x 1.81in) |
Weight: |
300g (0.66lbs) |
Warranty Standard: |
2 years |